Menü Schließen

SOLARMAX

SOLARMAX-error codes

Below you will find a list of common error messages from various brands. Not all error messages are listed here. It is advisable to also consult the manual of the device.
BrandError codeCauseAction
SolarmaxThe display remains blankDC disconnector Q1 is switched off.Switch on DC disconnector Q1.
SolarmaxThe display remains blankIrradiation too low.Wait until the irradiation is sufficient.
SolarmaxThe display remains blankStrings disconnected.Check PV generator and correct disconnection.
SolarmaxThe display remains blankInternal failure.Contact inverter service
SolarmaxThe display remains blankThe PV generator is connected incorrectly (plus and minus connections have been mixed up).Connect the PV generator properly.
SolarmaxFailure fanA fan is defective or dirty.Contact inverter service
SolarmaxTemperature limitationThe feed-in power has been temporarily reduced to limit the temperature of the inverter.Clean the fan grids and improve ventilation in the operations room.
SolarmaxFailure temp. sensorA temperature sensor in the inverter has failed.Contact inverter service
SolarmaxBurst errorThe inverter disconnected from the grid five times or more on the same day. The warning is displayed for the remainder of the day. The error counter will be reset when the system is restarted in the morning.Arrange for an electrician to check the grid instantaneous voltage and grid frequency. If you consider them to be in order, Contact inverter service
SolarmaxRTC errorThe RTC (real-time clock) in the inverter is malfunctioning, the date and time have been reset.If problem occurs repeatedly, Contact inverter service
SolarmaxFlash errorA flash error has occurred. Inverter mains operation continues to be guaranteed.Contact inverter service
SolarmaxFirmware mismatchThe firmware versions of the inverter controllers do not match.Contact inverter service
SolarmaxVdc too high (VDC3, VDC2, VDC1)The DC input voltage at the specified inverter DC connection is too high.Switch off the DC disconnector Q1 immediately and disconnect the PV generator from the inverter. Check the dimensioning of the PV generator.
SolarmaxNo mains No mains BPThere is no mains voltage or the AC supply has been interrupted.Check the AC supply.
SolarmaxMains error Mains error BPThe grid has been switched off.Arrange for an electrician to check the grid instantaneous voltage and grid frequency. If you consider them to be in order, Contact inverter service
SolarmaxFrequency too high Frequency too high BPThe mains frequency is outside of the f max 1 or f max 2 limit values.As long as the inverter is detecting a grid line to line over voltage: check the line to line voltages (with a true RMS measurement device). As long as you consider line to line voltages to be in order, Contact inverter service
SolarmaxFrequency too low Frequency too low BPThe mains frequency is outside of the f min 1 or f min 2 limit values.As long as the inverter is detecting a grid line to line over voltage: check the line to line voltages (with a true RMS measurement device). As long as you consider line to line voltages to be in order, Contact inverter service
SolarmaxVac too high (L1 L2 L3) Vac too high BP (L1 L2 L3)The mains voltage at the specified phase is outside of the Vac max 1 or Vac max 2 limit values.As long as the inverter is detecting a grid line to line over voltage: check the line to line voltages (with a true RMS measurement device). As long as you consider line to line voltages to be in order, Contact inverter service
SolarmaxVac too low (L1 L2 L3) Vac too low BP (L1 L2 L3)The mains voltage at the specified phase is outside of the Vac min 1 or Vac min 2 limit values.Arrange for an electrician to check the grid instantaneous voltage and grid frequency. If you consider them to be in order, Contact inverter service
SolarmaxVac 10min too high (L1 L2 L3) Vac 10min too high BP (L1 L2 L3)The maximum 10-minute average value of the mains voltage (Vac 10 min max.) at the specified phase is too high.Do nothing. The inverter will acknowledge the error auto matically. If problem occurs repeatedly, Contact inverter service
Solarmaxdf/dt too highThe change in the mains frequency per second has exceeded the maximum admissible value df/dt max.Do nothing. The inverter will acknowledge the error auto matically. If problem occurs repeatedly, Contact inverter service
SolarmaxInsulation fault DC Insulation fault DC BPThe insulation resistance of the PV generator against earth is too low.Check system isolation. If you consider the isolation impedance to be in order, Contact inverter service
SolarmaxIerr too high Ierr too high BPThe DC leakage current has exceeded the admissible absolute limit value lerr max.Check the PV generator.
SolarmaxIerr step too high Ierr step too high BPThe DC leakage current has exceeded the admissible step value.Please check the DC wiring and measure. If you consider the wiring to be in order, Contact inverter service
SolarmaxL and N interchangedA phase and the neutral conductor are incorrectly connected (interchanged).Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
SolarmaxError DC polarityOne or more DC connections are connected incorrectly (incorrect polarity).Please check the DC wiring and measure. If you consider the wiring to be in order, Contact inverter service
SolarmaxError ext. input 1The external grid monitoring and/or remote shutdown has disconnected the inverter from the grid.If constant, Contact inverter service
SolarmaxDevice error (+ error code)An internal error has occurred in the inverter.Contact inverter service
SolarmaxExternal blockingThere is a 0% command from MaxRemote (coming from the grid operator).Do nothing. The inverter will acknowledge the error auto matically. If problem occurs repeatedly, Contact inverter service
SolarmaxProgram FirmwareAn internal error has occurred in the inverter.The inverter firmware is currently being updated.
SolarmaxError 42An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 11An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 13An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 23An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 37An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 53An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 63An internal error has occurred in the inverter.Contact opnemen met omvormer service
SolarmaxError 73An internal error has occurred in the inverter.Contact opnemen met omvormer service