KACO-error codes

Below you will find a list of common error messages from various brands. Not all error messages are listed here. It is advisable to also consult the manual of the device.
BrandError codeCauseAction
KacoOS 1Self-test: The grid parameters and generator voltage are being checked.If problem occurs repeatedly, Contact inverter service
KacoOS 2Insufficient generator voltage and power, status before the transition to night shutdownIf problem occurs repeatedly, Contact inverter service
KacoOS 8Checks the shutdown of the power electronics as well as the grid relay before feed-in mode.If problem occurs repeatedly, Contact inverter service
KacoFS 10In case of overheating, the inverter switches off. Possible causes: • Excessively high ambient temperature • Fan covered • Inverter defective.Check the inverter for heat build up or blockage of the cooler ribs and rectify as required. If this does not correct the problem, Contact inverter service
KacoOS 11Power limitation: If the generator power is too high, the inverter limits itself to the maximum power (e.g. around noon if the generator capacity is too large).If problem occurs repeatedly, Contact inverter service
KacoFS 17The activated grid and system protection has been tripped.If problem occurs repeatedly, Contact inverter service
KacoFS 18Residual current was detected. The feed-in was interrupted.Contact inverter service
KacoFS 19There is an insulation fault on the PV generator. The feed-in was interrupted.Please check the DC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 30The current and voltage measurements in the inverter are not within acceptable range.If problem occurs repeatedly, Contact inverter service
KacoFS 32The internal grid separation relay test has failed.If problem occurs repeatedly, Contact inverter service
KacoFS 33The DC feed-in has exceeded the permitted value. This DC feed-in can be caused by grid conditions and may not necessarily indicate a fault.If problem occurs repeatedly, Contact inverter service
KacoFS 34A communication error has occurred in the internal data transmission.If problem occurs repeatedly, Contact inverter service
KacoFS 35Protective shutdown of the software (AC overvoltage, AC overcurrent, DC link overvoltage, DC overvoltage, DC overtemperature).Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 36Protective shutdown of the hardware (AC overvoltage, AC overcurrent, DC link overvoltage).Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 38The voltage of the DC generator is too high. The PV generator is configured incorrectly.If problem occurs repeatedly, Contact inverter service
KacoFS 40The voltage of a grid phase is too low;If problem occurs repeatedly, Contact inverter service
KacoFS 41the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 42the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 43the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 44the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 45the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 46the grid cannot be fed into. The phase experiencing failure is displayed.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 47The measured line-to-line voltage is outside of the tolerance limits.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 48Grid frequency is too low. This fault may be grid-related.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 49Grid frequency is too high. This fault may be grid-related.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 50The grid voltage measurement according to EN 50160 has exceeded the maximum permitted limit value. This fault may be grid-related.Please check the AC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoFS 57Waiting time of the inverter after a fault.This text is displayed for in formation purposes only.
KacoFS 58The temperature inside the unit was too high. The inverter switches off to prevent damage to the hardware.Check the inverter for heat build up or blockage of the cooler ribs and rectify as required. If this does not correct the problem, Contact inverter service
KacoFS 59A fault occurred during a self-test.1.) Switch off device with DC disconnector. 2.) Wait until the display has turned off completely. 3.) Switch on device with DC disconnector. If this does not rectify the error, Contact inverter service
KacoOS 60The inverter does not begin feeding into the grid until the PV voltage falls below a specified value.Please check the DC wiring and measure. If you consider the wiring to be in order, Contact inverter service
KacoOS 61The external limit Power control was activated by the grid operator. The inverter limits its power.This text is displayed for in formation purposes only.
KacoOS 63P(f)/frequency-dependent power reduction: Frequency-dependent power reduction will be activated when the BDEW (German Association of Energy and Water Industries) Medium Voltage Directive goes into effect. Power reduction starts at a frequency of 50.2 Hz.This text is displayed for in formation purposes only.
KacoOS 64Output current limiting: The AC current is limited once the specified maximum value has been reached.This text is displayed for in formation purposes only.
KacoFS 67There is a fault in the power section.Contact inverter service
KacoFS 70The fan is malfunctioning.Visual check: cooling circuit air supply. If the blockage cannot be rectified, Contact inverter service
KacoFS 73Standalone mode was detected.This text is displayed for in formation purposes only.
KacoOS 74The grid operator limits the feed-in power of the inverter.This text is displayed for in formation purposes only.
KacoOS 79PV generator’s insulation is being measuredThis text is displayed for in formation purposes only.
KacoFS 80The insulation measurement cannot be performed because the generator voltage is too volatile.This text is displayed for in formation purposes only.
KacoFS 81, 82, 83Overvoltage has been detected on a conductor. An internal protective mechanism has disconnected the device to protect it against damage.If problem occurs repeatedly, Contact inverter service
KacoFS 84A voltage deviation has been found in the DC link. An internal protective mechanism has disconnected the device to protect it against damage.If problem occurs repeatedly, Contact inverter service
KacoFS 85A voltage deviation has been found in the DC link. An internal protective mechanism has disconnected the device to protect it against damage.If problem occurs repeatedly, Contact inverter service
KacoFS 86Overvoltage has been found in the DC link. An internal protective mechanism has disconnected the device to protect it against damage.If problem occurs repeatedly, Contact inverter service
KacoFS 87,88,89A current that has been found on a conductor is too high. An internal protective mechanism has disconnected the device to protect it against damage.If problem occurs repeatedly, Contact inverter service
KacoFS 93,94The control board is defective.Contact inverter service
KacoFS 95,96The power section is defective.Contact inverter service
KacoFS 97Too much power has been fed into the grid. Complete disconnection of the device.Contact inverter service
KacoFS 98An internal protective mechanism has disconnected the device to protect it against damage. Complete disconnection of the device.Contact inverter service
KacoFS 99An internal protective mechanism has disconnected the device to protect it against damage. Complete disconnection of the device.Contact inverter service
KacoFS 100The device has been switched off because the temperatures in the housing were too high.Check temperature of direct surroundings and reduce this as required.
KacoFS 101The unit has shut down because of implausible internal measured values.Contact inverter service
KacoFS 102The unit has shut down because of implausible internal measured values.Contact inverter service
KacoFS 103The unit has shut down because of implausible internal measured values.Contact inverter service
KacoFS 104The unit has shut down because of implausible internal measured values.Contact inverter service
KacoFS 105The unit has shut down because of implausible internal measured values.Contact inverter service
KacoFS 106The unit has shut down because of implausible internal measured values.Contact inverter service